RE-TRANSMITTED ANALOG OUTPUT (Optional)
The re-transmitted analog output option transmits a digitally
programmable 4 to 20 mA or 0 to 10 VDC signal to drive chart recorders,
remote indicators and controllers. The option is contained on the upper PCB
and has two outputs, “ANALOG-” (TBB #10) and “ANALOG+” (TBB #11)
and is self-powered (active) with a compliance of 10 VDC. The analog “-”
output is isolated from the input common, eliminating problems from ground
loops. Programming of the option is performed in “Pro 8” of the normal
programming mode. Display values are simply keyed in to providea4mAor
0 VDC output, “AN-Lo”, and a 20 mA or 10 VDC output, “AN-HI”. The
analog output then follows the assigned value and as such will update every
measurement cycle. Nonstandard current or voltage ranges can be supported
by calculating the slope and intercept of the display/output and calculating
the required display values at 4 mA or 0 VDC and 20 mA or 10 VDC. Reverse
action can be achieved by programming a “high” display value for “AN-Lo”
and a “low” display value for “AN-HI”.
If the display should indicate an “OLOLOL”, “ULULUL”,or“SHort” the
analog output will go to 20 mA or 10 VDC for an “OLOLOL” or “SHort”, and
4mAor0VDCfora“ULULUL”.
Note: Analog “-” must be kept isolated from Alarm Comm. (TBB #8).
-33-
ANALOG OUTPUT DIAGRAMS